MAX+ 2KVA72V IB
Manufacturer specifications for this model.
| Product type | Online UPS |
|---|---|
| Capacity | 2KVA/1800W |
| Input voltage range | 110VAC±5% ~ 300VAC±5% |
| Input frequency range | 40Hz~70Hz |
| Phase | Single Phase with Ground |
| Input power factor | ≥0.99 @ Full Load |
| Output voltage | 200/208/220/230/240VAC |
| AC voltage regulation | ±1%(Battery Mode) |
| Battery-mode frequency | 50Hz±0.25Hz or 60Hz±0.3Hz |
| Current crest ratio | 3:1 |
| Harmonic distortion | ≤2% THD(Linear Load); 4% THD(Non-Linear Load) |
| Overload 105–110% | UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal. |
| Overload 110–130% | UPS shuts down after 1 minute at battery mode or transfer to bypass when the utility is normal. |
| Overload >130% | UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal. |
| Transfer AC to battery | Zero |
| Inverter to bypass | <4ms(Typical 2.5ms) |
| Battery mode waveform | Pure Sine Wave |
| Efficiency | 90% |
| Battery DC voltage | 72VDC/IB(6Battery 7Ah inside) |
| Charge current | 1.5A~9.5A |
| Selectable charging current | 2.0A/4.0A/6.0A/8.0A(Maximum) Selectable via LCD setting |
| Dimensions (L x W x H) | 421x190x318 in mm |
| IB net weight | 25.8Kgs. |
| Operating humidity | 20–95% RH@0–40 C (Non-Condensing) |
| Noise level | Less than 50dBA@1Meter (With Fan Speed Control) |
| Display | LCD Indications |
| Management | SMART RS-232 OR USB |
| Optional SNMP | Power Management from SNMP Manager and Web Browser |
| Management software OS listing (undated datasheet) | Windows 2000/2003/XP/Vista/2008/7/8; Linux; Unix; MAC. Historical manufacturer listing only; current OS/driver support or software licence entitlement not established. |
| Architecture | High-frequency online double-conversion IGBT |
| Output power factor | 0.9 |
| Static bypass | Supported |
| Hot standby | Manufacturer lists hot standby feature |
| Programmable power management outlets | Supported |
| Frequency converter mode | 50 Hz / 60 Hz |
| Generator compatibility | Supported |
| EMI / RFI filtering | Noise filter |
| Overvoltage protection | Inbuilt overvoltage cutoff with surge protection |
| External charger | Optional; manufacturer lists capacity expansion to 8 A |
| Power | 1800W |
| UPS Apparent Power | 2000 VA |
| UPS Topology | Online double-conversion |